See the adopted code for the complete text ( for copies contact the International
Code Council at thier web site).
CLOTHES DRYERS EXHAUST
1. Dryer exhaust systems shall be independent of all other systems, shall convey the moisture to the outdoors and shall terminate on the outside of the building. Exhaust duct terminations shall be in accordance with the dryer
manufacturers installation instructions. Screens shall not be installed at the duct termination. Exhaust ducts shall not be con-
nected with sheet-metal screws or fastening means which extend into the duct. Exhaust ducts shall be equipped with a back-
draft damper. Exhaust ducts shall be constructed of minimum 0.016-inch-thick (0.406 mm) rigidmetal ducts, having smooth
interior surfaces with joints running in the direction of air flow. Flexible transition ducts used to connect the dryer to the exhaust duct system shall be limited to single lengths, not to exceed 8 feet (2438 mm) in length and shall be listed and labeled in accordance with UL 2158A. Transition ducts shall not be concealed within construction.
Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers.
2. Exhaust duct size. The diameter of the exhaust duct shall be as required by the clothes dryer’s listing and the
manufacturers installation instructions.
3. Length limitation. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the EXHAUST SYSTEM REQUIREMENTS Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible metal duct and approved vent hood which has a swing-out damper(s) that open when the dryer is in operation. When the dryer stops, the dampers automatically close to prevent drafts and the entrance of insects and rodents. To avoid restricting the outlet, maintain a minimum of 12 inches (30.5 cm) clearance between the vent hood and the ground or any other obstruction. GENERAL ELECTRIC: http://lib.store.yahoo.net/lib/usappliance/GLEQ2152install.pdf Clothes Dryer Fire Prevention A Final Note: Carbon Monoxide Detectors and Smoke Alarms save
dryer location to the wall or roof termination. The maximum length of the duct shall be reduced 2.5 feet (762 mm) for each
45-degree (0.79 rad) bend and 5 feet (1524mm)for each 90-degree (1.6 rad) bend. The maximum length of the exhaust duct does not include the transition duct.
Exceptions:
1. Where a clothes dryer booster fan is installed and listed and labeled for the application, the maximum length of the exhaust duct, including any transition
duct, shall be permitted to be in accordance with the booster fan manufacturer’s installation instructions.
Where a clothes dryer booster fan is installed and not readily accessible from the room in which the dryer is located, a permanent identifying label shall be placed
adjacent to where the exhaust duct enters the wall. The label shall bear the words This dryer exhaust system is equipped with a remotely located booster fan.
2. Where the make and model of the clothes dryer to be installed is known and the manufacturers installation instructions for such dryer are provided to the building official, the maximum length of the exhaust duct, including any transition duct, shall be permitted to be in accordance with the dryer manufacturers installation instructions.
***************************************************
All Leading Manufacturer's require the dryer vent to terminate at least 12-inches from ground or any other object. A list of these manufacturer's is below:
MAYTAG: See Manufacturer's Installation Instructions at : http://www.maytag.com/assets/product/W10099070.PDF page 14 & 15. " Exhaust hoods must be at least 12" from the ground or any object that may be in the path of the exhaust...."
FRIGIDARE: http://lib.store.yahoo.net/lib/usappliance/GLEQ2152install.pdf
WHIRLPOOL / KENMORE: See: Whirlpool Installation Manual : http://www.whirlpool.com/assets/pdfs/product/ZVENTI/W10100920.pdf
ASKO:
http://www.us-appliance.com/askolaundry.html
SAMSUNG: http://www.us-appliance.com
MIEL:
http://www.us-appliance.com/mielelaundry.html
*********************************************
lives. We as building inspectors, contractors and
consumers have known this for years. But we must
remain diligent in or training and education efforts.